Customization: | Available |
---|---|
After-sales Service: | New One Replace Within One Year |
Warranty: | 3 Years |
Still deciding? Get samples of US$ 28/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Current | Phase current |
Voltage | L-N |
Frequency | 45 to 65Hz |
Power | Active power |
Power factor | Power factor |
Data update rate | 1 second | |
Input-Voltage | Rate voltage (Un) |
230 Vac |
Direct connection | Measured range : 85 to 270 Vac | |
Frequency range | 45 to 65 Hz | |
Overload capacity | 2*Un for 1 second | |
Input-Current | Measured range | 0.005 to 80 A, basic current (Ib) is 5A |
Overload capacity | 30*Imax for 0.01 second | |
Pulse output | Interface type | Open collector optocoupler |
Pulse constant | 1000 / 100 / 10 / 1 imp/kWh(kvarh) (Configurable) | |
Pulse width | 60/100/200 milliseconds (Configurable), default is 100milliseconds | |
Pulse output type | Import/export/total active energy, Import/export/total reactive energy (Configurable) |
|
Class | Class A, according IEC 62053-31 | |
Input voltage | 5 ~ 27 Vdc | |
Pulse indicator light on the panel | Pulse constant is 1000imp/kWh | |
Real-time clock accuracy | 0.5 s/d |
Mechanical Characteristics | |
IP Degree of Protection (IEC 60529) | Designed to IP51 front display, IP30 meter body |
Dimensions (W X H X D) | 36 x 100 x 65 mm |
Mounting Position | DIN Rail mounting |
Material of meter case | UL 94 V-0 |
Environmental Characteristics | |
Operating Temperature | -25 to +55ºC |
Storage Temperature | -40 to +80ºC |
Humidity | < 90%, non-condensing |
Pollution Degree | 2 |
Altitude | Up to 2000m |
Vibration | 10 Hz to 150Hz, IEC 60068-2-6 |
Wireless communication | |
Interfaces standard and protocols | 2-wire RS485, Modbus RTU Optional: MBus |
Buad rate | 1200 to 38400 bps, default is 9600 bps |
Parity bit | None, Even, Odd, default is None |
Stop bit | 1 or 2, default is 1 |
Response time | <100ms |
Transmission mode | half-duplex |
Transmission distance | Up to 1000m |
Max. Bus loading | 64 pcs |