Customization: | Available |
---|---|
After-sales Service: | New One Replace Within One Year |
Warranty: | 3 Years |
Still deciding? Get samples of US$ 49/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Input-Voltage | Rate voltage (Un) |
230 Vac (L-N) / 400 Vac (L-L) |
Measured range (Direct connection) |
30 to 350 Vac (L-N), 30 to 660 Vac (L-L) | |
PT primary | 30 to 600000 | |
Impedance | 1MΩ | |
Frequency range | 45 to 65 Hz | |
Overload capacity | 2*Un for 1 second | |
Input-Current | CT2 (Secondary) | 1A or 5A Optional: 100mA, 100mV |
CT1 (Primary) | 1 to 9999 A | |
Measured range | 0.003 to 6 A, basic current (Ib) is 5A | |
Impedance | <0.01 ohm | |
Overload capacity | 120A for 0.5 second | |
Burden | <0.06VA at 6A | |
Auxiliary power supply | Operating range | 80 ~ 300 Vac / 100 ~ 420 Vdc |
Frequency | 45 ~ 65 Hz | |
Power consumption | < 4VA/0.5W |
Digital input (DI) |
Number | 4 |
Type | Support dry contact input (built-in power supply: 20 ~ 24VDC) | |
Input Resistance | 10kΩ | |
Maximum frequency | 250Hz | |
Response time | 2 milliseconds | |
Isolation | 2.5 kVrms | |
Digital output (DO) |
Number/Type | 2 - electromagnetic relay |
Output frequency | 10Hz maximum | |
Switching current | 250 Vac at 3.0 Amps, 100k cycles | |
Isolation | 2.5 kVrms | |
Pulse output | Interface type | Open collector optocoupler |
Pulse constant | Per pulse equal 0.001/0.01/0.1/1/10/100/1000 kWh/kvarh (Configurable) | |
Pulse width | 60/100/200 milliseconds (Configurable), default is 100milliseconds | |
Pulse output type | Import/export/total active energy, Import/export/total reactive energy (Configurable) |
|
Class | Class A, according IEC 62053-31 | |
Input voltage | 5 ~ 27 Vdc | |
Pulse indicator light on the panel | Pulse constant is 5000imp/kWh, Represents the total active energy of the secondary side | |
Real-time clock accuracy | 1.0 s/d |
Mechanical Characteristics | |
IP Degree of Protection (IEC 60529) | Designed to IP51 front display, IP30 meter body |
Dimensions (W X H X D) | 96 x 96 x 70 mm (depth of meter from housing mounting flange) 96 x 96 x 14 mm (protrusion of meter from housing mounting flange) |
Weight | PAC5000: 350g. PAC5010: 360g. PAC5100: 390g. PAC5110: 400g. |
Mounting Position | Vertical |
Panel thickness | 1 ~ 5 mm |
Material of meter case | UL 94 V-0 |
Communications | |
Interfaces standard and protocols | 2-wire RS485, Modbus RTU Optional: MBus |
Buad rate | 1200 to 38400 bps, default is 9600 bps |
Parity bit | None, Even, Odd, default is None |
Stop bit | 1 or 2, default is 1 |
Response time | <100ms |
Transmission mode | half-duplex |
Transmission distance | Up to 1000m |
Max. Bus loading | 64 pcs |
Firmware Update | Support communication port to update firmware |